Fronius Galvo 3.1-1 light

  • ArtikelNr.: AR688
  • Artikelgewicht: 16,80 kg
  • Lieferzeit: 4 - 14 Werktage
  • Unser Preis : 1.177,50 €
  • inkl. 20% USt., zzgl. Versand (Spedition Kleingerät)
Wird geladen ...

Kategorie:

Beschreibung

Max. input current (Idc max) 20.7 A
Max. array short circuit current 31.0 A
Min. input voltage (Udc min) 165 V
Feed-in start voltage (Udc start) 185 V
Nominal input voltage (Udc,r) 330 V
Max. input voltage (Udc max) 550 V
MPP voltage range (Umpp min - Umpp max) 165 - 440 V
Number of MPP trackers 1
Number of DC connections 3
OUTPUT DATA 
AC nominal output (Pac,r) 3,100 W
Max. output power 3,100 VA
Max. output current (Iac max) 15.0 A
Grid connection (voltage range) 1~NPE 230 V (+17 % / 20 %)
Frequency (frequency range) 50 Hz / 60 Hz (45 - 65 Hz)
Total harmonic distortion < 4 %
Power factor (cos fac,r) 0.85 - 1 ind. / cap.
GENERAL DATA 
Dimensions (height x width x depth) 645 x 431 x 204 mm
Weight 16.8 kg
Degree of protection IP 65
Protection class 1
Over voltage category (DC / AC)*) 2 / 3
Night-time consumption < 1 W
Inverter concept HF transformer
Cooling Regulated air cooling
Installation Indoor and outdoor installation
Ambient temperature range -25°C to +50°C
Permitted humidity 0 % to 100 %
Max. altitude 2,000 m / 3,500 m (unrestricted / restricted voltage range)
DC connection technology Screw terminal connection 2.5 mm² - 16 mm²
Mains connection technology Screw terminal connection 2.5 mm² - 16 mm²
Certificates and complience with standards ÖVE / ÖNORM E 8001-4-712, AS 4777-2, AS 4777-3, AS3100, DIN V VDE 0126-1-1/A1, VDE AR N 4105, IEC 62109-1-2, IEC 62116, IEC 61727, CER 06-190, CEI 0-21, EN 50438, G83, G59
EFFICIENCY 
Max. efficiency 96.1 %
PROTECTION DEVICES 
DC insulation measurement Warning / shutdown (depending on country setup) at Riso < 600 kO
Overload behavior Operating point shift, power limitation
DC circuit breaker Included
INTERFACES 
WLAN / Ethernet LAN Fronius Solar.web, Modbus TCP SunSpec,´Fronius Solar API (JSON)
6 inputs and 4 digital inputs/outputs Interface to ripple control receiver
USB (A socket) Datalogging, inverter update via USB flash drive
2 x RS422 (RJ45 socket) Fronius Solar Net, Interface protocol
Signalling output Energy management (floating relay output)
Datalogger and Webserver Included
RS485***) Modbus RTU SunSpec or meter connection

LiveZilla Live Chat Software